FIRE SUPPRESION SYSTEM
NFPA DESIGN SPESIFICATION
HIGHEST RISK CLASSIFICATION
-Risk Group A/B
ROOF DENSITY
- 12.2mm/min over 270sqm
- Based on for Group A/B
- K 11.5, 20mm (k8.0) Sprinkler Heads
- Foam sprinkler system - AFFF - AR 3% Foam Additive
- 1900 L/min Hose Stream Allowance to added
CEILING & IN-RACK/SHELF PROTECTION
- Group A/B
- 3m max Horizontally spaced
- 1 Row in flue space-In-Rack Protection
- 1 Level over 2nd Tier
- Starting Flow - 114 L/min (based on a K8 (K5.6) with starting pressure of 200kPa
- 1 X Rack: 6 Sprinklers on 3 Tier Levels = 18 Heads in Opperation
PUMP REQUIRED
- 1 X NFPA 2500 GPM Diesel Pump
- 1 X NFPA 2500 GPM Electric Pump
DESIGN RESULT
ROOF SPRINKLERS OVER IN RACKS
- The ceiling sprinklers should be placed with a maximum head spacing of 9.3sqm per sprinkler. The maximum spacing between sprinklers should be at least 1.8m
- K 11.5 / 20mm Upright Spray
HYDRAULIC RESULT
- AREA: 3920 sqm
- SPRINKLERS: 550 in roof / ceiling
- AVG SPACING: 7.127 sqm
- MAXIMUM: 8.89 sqm
- Sprinklers in opperation: 270/7.127 = 38 heads in operation
- Starting flow / sprinkler : 12.2 x 8.89 sqm = 108.5 L/min
- Remote: 9717 L-MIN @ 479 kPa w/hose stream
TANK CAPACITY
- Based on Workshop Demand x 120min
- 9717 x 120min = 584 cubic meters effective capacity/tank
- Circular Steel Tank : Total Volume - 600 Cubic Meter / tank x 2